AS-Interface utilizes a single, trapezoidal,
unshielded two-wire cable, which eliminated the extensive parallel
control wiring required with most installations. The existing controller
sees AS-Interface as remote I/O; therefore, AS-Interface connect to
the existing network with minimal programming changes.
The AS-Interface system utilizes only
one master per network to control the exchange of data. This allows
the master to interrogate up to 31 slaves and update all I/O information
within 5 ms (10 msec for 62 slaves). For slave connection, an insulated
two-wire cable is recommended to prevent reversing polarity. The electrical
connection is made using contacts which pierce the cable's insulation,
contacting the two wires, thus eliminating the need to strip the cable
and wire to screw terminals. For data exchange to occur, each slave
must be programmed with an address which is stored internally in non-volatile
memory and remains even after power is removed.
The maximum cable length
for each master is 100 m without repeaters. Using repeaters, distances
to 300 m are possible.
|